Business Areas

Best technology in clean hydrogen energy, high pressure gas, disaster prevention business, safety equipment

Gaseous Fire Extinguishing System

NKFS-LPCO₂

It is a facility for suppressing of fire through suffocation and cooling action by releasing CO₂ into the protection zone at the time of breakout of the fire by storing CO₂, a nonflammable gas, in storage tank under the pressure of 2.1MPa at the temperature of -18℃.

Appearance and Features

성상 및 특징 표
Area Reduction It is possible to reduce the area of the storage container room to less than 50% of the pressurized type.
Manual Control Possible It is possible to control the release of gas through manual operation and stop at the time of occurrence of erroneous operation.
Always Check The Charge Level It is possible to check the quantity of charged chemical agent at any time.
Reduced Recovery Time and Costs It is possible to reduce the time and cost of restoration since it is possible to recharge the chemical agent simply by using tank lorry.

NKFS-LPCO₂ design specifications

설계사양 표
Material KS D3521, SPPV490(ASTM A516-70), KS D3541, SLA360 or higher than equivalent Specification Applied KGS code AC111, KS B6733
Releasing Format Total releasing format, local release format, hose reel format Storage Container 0.5 ~ 50 Ton
Applied Fire A, B and C ratings Charging Pressure 2.1MPa @ -18℃
Maximum Installation Height Of Nozzle 14m x14m Operating Pressure More than 2.59MPa
Release Time Surface fire (1 minute) Deep fire (7 minutes) Design Temperature -20℃ ~40℃
Program GSI(USA)